title: "Amp Calculator – Watts, kW or Horsepower to Amps | FigureYard"
description: "Convert watts, kilowatts, horsepower or kVA to amps for DC, single-phase and three-phase circuits, with power factor and motor efficiency taken into account."
url: https://figureyard.com/energy/amp-calculator/
image: https://figureyard.com/og/energy/amp-calculator.png
---

[Electrical, Heating & Insulation](https://figureyard.com/energy/)

# Amp Calculator

Pick the kind of circuit, enter the power and the voltage, and you get the current in amps, with the apparent power and the current a wire and breaker must carry if the load runs for hours.

Reviewed by FigureYard editorial team · Updated October 12, 2026 · 10 sources

*Interactive calculator on the page (inputs: Circuit; Power is given in; Power; Voltage; Power factor (1 for heaters and lights); Motor efficiency (%)). The results below are for its default inputs.*

**Current**

**12.5** amps

- Power drawn: **1,500** watts
- Apparent power: **1.50** kVA
- Wire and breaker must carry, if it runs for hours: **15.6** amps

Current is power divided by voltage, with two corrections for AC: the power factor, which is one for heaters and lights but lower for motors, and for three-phase circuits the square root of three.

## How to use this calculator

1. Choose DC, single-phase AC (a household circuit) or three-phase AC.
2. Choose how the power is given and enter it: watts, kilowatts, a motor's horsepower or kVA.
3. Enter the voltage. For a motor, set its power factor and efficiency under More options, from the nameplate if you have it.

## Worked examples

### A space heater

Circuit: Single-phase AC (household) · Power is given in: Watts · Power: 1,500 · Voltage: 120 V

- Current: 12.5 amps
- Power drawn: 1,500 watts
- Apparent power: 1.50 kVA
- Wire and breaker must carry, if it runs for hours: 15.6 amps

### An electric dryer

Circuit: Single-phase AC (household) · Power is given in: Watts · Power: 5,000 · Voltage: 240 V

- Current: 20.8 amps
- Power drawn: 5,000 watts
- Apparent power: 5.00 kVA
- Wire and breaker must carry, if it runs for hours: 26.0 amps

### A one-horsepower pump

Circuit: Single-phase AC (household) · Power is given in: Horsepower (a motor) · Power: 1 · Voltage: 240 V · Power factor: 0.9

- Current: 4.18 amps
- Power drawn: 903 watts
- Apparent power: 1.00 kVA

### A three-phase load

Circuit: Three-phase AC · Power is given in: Kilowatts · Power: 15 · Voltage: 208 V · Power factor: 0.9

- Current: 46.3 amps
- Power drawn: 15,000 watts
- Apparent power: 16.67 kVA
- Wire and breaker must carry, if it runs for hours: 57.8 amps

### A car inverter

Circuit: DC (batteries, solar, cars) · Power is given in: Watts · Power: 300 · Voltage: 12 V

- Current: 25.0 amps
- Power drawn: 300 watts
- Wire and breaker must carry, if it runs for hours: 31.3 amps

## The formulas

- DC: amps = watts ÷ volts.
- Single-phase AC: amps = watts ÷ (volts × power factor).
- Three-phase AC: amps = watts ÷ (volts × power factor × 1.73), the square root of three, with the line-to-line voltage.
- Horsepower: one horsepower is 745.7 watts; divide by the motor's efficiency for the power it draws.

## Power factor and efficiency

Heaters, incandescent bulbs and other resistive loads have a power factor of 1, so watts and volt-amps are the same. Motors draw some current that does no work: a University of Kentucky review puts refrigerators around 0.8 to 0.99 and central air conditioning around 0.9 to 0.92, and a motor's power factor drops further when it runs below about 65 percent of its load.

A motor's horsepower is what it delivers at the shaft. Federal rules require a one-horsepower capacitor-start motor to be at least 82.6 percent efficient, so it draws more than its rating; the calculator divides by the efficiency.

## From amps to wire and breaker

A load that runs at full current for 3 hours or more counts as continuous, and the wire and breaker for it must carry 125 percent of its current. The wire size calculator takes it from there.

## Common questions

### How do I convert watts to amps?

Divide the watts by the volts for a DC or resistive load. For AC loads with motors, divide by the power factor too. A heater of fifteen hundred watts on a hundred-twenty-volt circuit draws twelve and a half amps.

### How many amps does a horsepower motor draw?

Multiply the horsepower by 745.7 watts, divide by the motor's efficiency and power factor, then by the voltage. The nameplate gives the full-load amps directly. To size the wire and breaker, an electrician uses the full-load current in the electrical code's motor tables, which is often higher than this estimate for a small motor.

### What is the formula for three-phase amps?

Amps = watts ÷ (volts × power factor × 1.73), using the line-to-line voltage.

### How do I calculate amps needed for a house?

Add up the watts of everything that can run at once and divide by the service voltage. For sizing a service, an electrician uses the code's load calculation, which allows for not everything running together.

### How many amps does a refrigerator use?

A typical frost-free refrigerator draws about 725 watts while its compressor runs, which is about 6 amps at 120 volts. Its motor's power factor of about 0.895 makes the current a little higher, and the compressor takes a short surge each time it starts.

### How many amps does a microwave use?

A microwave oven draws about 925 watts from the outlet, which is about 7.7 amps at 120 volts.

### How many amps does an electric dryer use?

An electric clothes dryer uses about 3,400 watts, which is about 14.2 amps at 240 volts. That is why it has a circuit of its own, usually protected at 30 amps, the most that 10 AWG copper wire may carry.

### How many amps does a window air conditioner use?

A window unit of about ten thousand BTU uses about 1,000 watts while it runs, which is about 8.3 amps at 120 volts.

### How many amps does a washing machine use?

A clothes washer draws about 350 to 500 watts while it runs, which averages about 3.5 amps at 120 volts. Its motor's power factor, about 0.57, raises the current the circuit carries to about 6.2 amps, and that is the figure to use for the circuit.

## Related calculators

- [Wire Size Calculator](https://figureyard.com/energy/wire-size-calculator/)
- [Voltage Drop Calculator](https://figureyard.com/energy/voltage-drop-calculator/)
- [Generator Size Calculator](https://figureyard.com/energy/generator-size-calculator/)

Reviewed by FigureYard editorial team on 2026-10-09. Formulas are tested against published values, and material figures come from the sources below. [How we build our calculators](https://figureyard.com/editorial-policy/).

## Sources

- [NIST Guide to the SI, Appendix B.8: Factors for units listed alphabetically](https://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors/nist-guide-si-appendix-b8)
- [University of Kentucky, SPARK Laboratory (ECE Department): Power Factor and Reactive Power in US Residences: Survey and EnergyPlus Modeling (Table I)](https://sparklab.engr.uky.edu/sites/spark/files/2021_1001_ICRERA2021_ReactivePowerandPF_SEJ.pdf)
- [U.S. Department of Energy (Code of Federal Regulations, 1 January 2013 edition): 10 CFR 431.446 Small electric motors energy conservation standards and their effective dates](https://www.govinfo.gov/content/pkg/CFR-2013-title10-vol3/pdf/CFR-2013-title10-vol3-sec431-446.pdf)
- [Electrical License Renewal (reproduces NEC 210.19(A)(1) text): 210.19(A)(1) Branch Circuits.](https://www.electricallicenserenewal.com/Electrical-Continuing-Education-Courses/NEC-Content.php?sectionID=818)
- [Michigan State University, Biosystems & Agricultural Engineering Department: Electrical Tech Note 226: Power Factor](https://www.maec.msu.edu/application/files/1117/1923/9646/Tech_Note_226_Power_Factor.pdf)
- [U.S. Department of Energy, Advanced Manufacturing Office (prepared by the Washington State University Energy Program): Premium Efficiency Motor Selection and Application Guide: A Handbook for Industry](https://www.energy.gov/sites/prod/files/2014/04/f15/amo_motors_handbook_web.pdf)
- [IAEI (International Association of Electrical Inspectors), IAEI Magazine, Focus on the Code: Are there any practical guidelines available to installers and the enforcement community with regards to continuous loads?](https://iaeimagazine.org/columns/focus-on-the-code/are-there-any-practical-guidelines-available-to-installers-and-the-enforement-community-with-regards-to-continuous-loads/)
- [Virginia Cooperative Extension, Virginia Tech: ENERGY SERIES: Estimating Appliance and Home Electronic Energy Use](https://www.pubs.ext.vt.edu/2901/2901-9014/2901-9014.html)
- [Encore Wire (Prysmian): Wire Ampacity Size Table](https://www.encorewire.com/products/tools-and-resources/calculators/wire-size-table.html)
- [Briggs & Stratton (brochure hosted by the dealer mygenerator.com.au): 2020 Portable Generators brochure (Home Essentials and Heating/Cooling wattage tables)](https://www.mygenerator.com.au/assets/images/resource/pdf/Briggs&Stratton_Generator_Brochure.pdf)