title: "Wire Size Calculator – AWG for Amps and Distance | FigureYard"
description: "Find the wire gauge for a circuit from its current, voltage and run length, with ampacity and voltage drop checked together, for copper and aluminum."
url: https://figureyard.com/energy/wire-size-calculator/
image: https://figureyard.com/og/energy/wire-size-calculator.png
---

[Electrical, Heating & Insulation](https://figureyard.com/energy/)

# Wire Size Calculator

Enter the current your load draws, the circuit voltage and the one-way distance to it. The calculator picks the smallest wire that carries the current and keeps the voltage drop in check over the run, and shows how the sizes around it compare.

Reviewed by FigureYard editorial team · Updated October 13, 2026 · 8 sources

*Interactive calculator on the page (inputs: The wire feeds; Load current; Circuit voltage; One-way distance; Conductor; Wire type; Runs for 3 hours or more at a time; Circuit; Allowed voltage drop (%)). The results below are for its default inputs.*

**Wire size**

**10 AWG** copper

- Current the wire must carry: **16.0** A
- Rated for: **30** A
- Voltage drop: **2.48** %
- Longest run within 3%: **91** ft

Each copper size for this circuit

| Size | Rated | Drop | Fits |
| --- | --- | --- | --- |
| 14 AWG | 15 A | 6.28% | Too small for the current |
| 12 AWG | 20 A | 3.96% | Too much drop |
| 10 AWG | 30 A | 2.48% | Yes |
| 8 AWG | 40 A | 1.56% | Yes |
| 6 AWG | 55 A | 0.98% | Yes |

A wire has to pass two separate tests. It must carry the current without overheating, which is its ampacity in the National Electrical Code table, and it must not lose too much voltage on a long run. On short runs the current sets the size; on long runs voltage drop often calls for a thicker wire.

## How to use this calculator

1. Enter the load current in amps. If you only know the watts, divide them by the voltage.
2. Tap the circuit voltage and enter the one-way distance from the panel to the load.
3. Pick copper or aluminum. For copper, choose NM-B cable, the usual cable inside walls, or single THHN wires in conduit: the code rates them from different columns of its table.
4. If the load runs at full current for 3 hours or more at a time, such as a car charger or a space heater, mark it as continuous. The wire must then carry 125 percent of the current.

## Worked examples

### A workshop circuit

Load current: 16 A · Circuit voltage: 120 V · One-way distance: 50 ft

- Wire size: 12 AWG copper
- Current the wire must carry: 16.0 A
- Rated for: 20 A
- Voltage drop: 2.64%
- Longest run within 3%: 57 ft

### A subpanel in a detached garage

Load current: 40 A · Circuit voltage: 240 V · One-way distance: 120 ft · Wire type: THHN/THWN wires in conduit (75 °C)

- Wire size: 6 AWG copper
- Current the wire must carry: 40.0 A
- Rated for: 65 A
- Voltage drop: 1.96%
- Longest run within 3%: 183 ft

### A car charger that runs for hours

Load current: 32 A · Circuit voltage: 240 V · One-way distance: 60 ft · Wire type: THHN/THWN wires in conduit (75 °C) · Runs for 3 hours or more at a time: Yes, a continuous load

- Wire size: 8 AWG copper
- Current the wire must carry: 40.0 A
- Rated for: 50 A
- Voltage drop: 1.24%
- Longest run within 3%: 145 ft

### A long aluminum feeder

Load current: 80 A · Circuit voltage: 240 V · One-way distance: 150 ft · Conductor: Aluminum

- Wire size: 1 AWG aluminum
- Current the wire must carry: 80.0 A
- Rated for: 100 A
- Voltage drop: 2.53%
- Longest run within 3%: 178 ft

## How the wire size is chosen

First comes ampacity: the current a wire may carry without overheating. NM-B cable is rated by the lowest temperature column of the code table, and single wires in conduit by the next one up, as long as the breaker and the device they connect to are rated for it. The thinnest sizes have one more limit: the code caps the breaker on 14 AWG copper at 15 amps, on 12 AWG at 20 amps and on 10 AWG at 30 amps, whatever the table says.

Then comes voltage drop. A branch circuit is commonly kept within 3 percent drop, so motors start and lights stay bright at the far end. The calculator works out the drop for each size over your run and keeps the larger of the two answers.

## When to go up a size

- The run is long: the table below the result shows how much each size drops, so you can see where it crosses the limit.
- Cables run through a hot attic, or more than three current-carrying wires share a conduit or bundle. The code then lowers the ampacity, which this calculator does not.
- The breaker or the device is rated only for the lowest temperature column. Many are rated for the higher one, but check the label.
- You plan to add load later. A size up costs little next to opening the walls again.

## Wire size for common circuits

Each of these pages opens the calculator set to one circuit, with a table of the size for every distance:

- [20 amp circuit](https://figureyard.com/energy/wire-size-for-20-amp/): 12 AWG copper, 10 AWG on a long run
- [30 amp circuit](https://figureyard.com/energy/wire-size-for-30-amp/): 10 AWG copper or 8 AWG aluminum, for dryers and water heaters
- [50 amp circuit](https://figureyard.com/energy/wire-size-for-50-amp/): 6 AWG copper cable or 8 AWG THHN, for ranges, RVs and car chargers
- [60 amp circuit](https://figureyard.com/energy/wire-size-for-60-amp/): 4 AWG copper cable or 6 AWG THHN, for subpanels and hot tubs
- [100 amp subpanel](https://figureyard.com/energy/wire-size-for-100-amp-subpanel/): 3 AWG copper or 1 AWG aluminum

## Wire size for a home's main service

The service conductors that carry a whole single-family house's load may be smaller than an ordinary feeder of the same rating, because the NEC (Table 310.12) lets them carry only 83 percent of the service rating. The table covers only that single-phase service or main feeder, with no corrections for heat; a feeder to a subpanel, a detached garage or one part of the house is sized from the regular ampacity table, the way the calculator above does it.

For the service of a whole house, the table gives:

- For a service rated 100 amps: 4 AWG copper or 2 AWG aluminum
- For a service rated 200 amps: 2/0 AWG copper or 4/0 AWG aluminum
- For a service rated 400 amps: 400 kcmil copper or 600 kcmil aluminum

## Common questions

### What size wire do I need for a twenty-amp circuit?

In copper NM-B cable, 12 AWG: the code allows a breaker of 20 amps on it. On a long run, voltage drop can call for 10 AWG instead, so enter your distance in the calculator.

### What size wire do I need for a fifty-amp circuit?

It depends on the cable and the run. Single copper wires in conduit at the higher temperature column usually come out at 8 AWG, and NM-B cable at 6 AWG. Enter your current and distance to check voltage drop too.

### Can I put 14 AWG wire on a twenty-amp breaker?

No. The code limits 14 AWG copper to a breaker of 15 amps, so a twenty-amp circuit needs 12 AWG or larger, even on a short run.

### Why is NM cable rated for less current than THHN wire?

NM-B cable bundles its wires in a jacket, often inside insulation, so the code rates it by its lowest temperature column. Single THHN wires in conduit may use the next column when the breaker and devices are rated for it, which allows more current for the same size.

### What is a continuous load?

One that runs at its full current for 3 hours or more, such as a car charger, a water heater or a space heater. The wire and breaker for it must be sized for 125 percent of that current.

### What size wire do I need for a 200 amp service?

For the service that feeds a whole single-family house, the NEC's dwelling table allows 2/0 AWG copper or 4/0 AWG aluminum for a rating of 200 amps. A feeder to a subpanel of the same rating needs bigger wire, sized from the regular ampacity table: 3/0 AWG copper carries 200 amps in wire and terminals rated for the higher-temperature column.

### What size wire do I need for a 100 amp subpanel?

A subpanel feeder is sized from the regular ampacity table, not the dwelling service table. In wire rated for the higher-temperature column, such as THWN conductors or SER cable, with terminals rated for it, 3 AWG copper carries 100 amps and 1 AWG aluminum 100 amps. NM-B cable is held to its lower-temperature rating and needs a larger size.

### What size wire do I need for a dryer?

An electric dryer usually has a circuit protected at 30 amps, which takes 10 AWG copper: the smallest copper wire the NEC allows on that breaker.

## Related calculators

- [Wire Size for a 100 Amp Service](https://figureyard.com/energy/wire-size-for-100-amp-service/)
- [Wire Size for a 200 Amp Service](https://figureyard.com/energy/wire-size-for-200-amp-service/)
- [Voltage Drop Calculator](https://figureyard.com/energy/voltage-drop-calculator/)
- [Electricity Cost Calculator](https://figureyard.com/energy/electricity-cost-calculator/)
- [BTU Calculator for Room Air Conditioners](https://figureyard.com/energy/btu-calculator/)
- [Conduit Fill Calculator](https://figureyard.com/energy/conduit-fill-calculator/)
- [Recessed Lighting Calculator](https://figureyard.com/energy/recessed-lighting-calculator/)

Reviewed by FigureYard editorial team on 2026-10-09. Formulas are tested against published values, and material figures come from the sources below. [How we build our calculators](https://figureyard.com/editorial-policy/).

## Sources

- [Michigan State University Electrical Tech Note 227: Sizing Conductors to Minimize Voltage Drop (Table 227.1, dc resistance at 75 °C)](https://www.maec.msu.edu/download_file/view/147/303)
- [Cerrowire Voltage Drop Table (rev. 09/2018)](https://www.cerrowire.com/wp-content/uploads/2018/09/Cerrowire_Voltage-Drop_210521.pdf)
- [Electrical License Renewal (reproduces NEC 210.19(A)(1) text): 210.19(A)(1) Branch Circuits.](https://www.electricallicenserenewal.com/Electrical-Continuing-Education-Courses/NEC-Content.php?sectionID=818)
- [Encore Wire (Prysmian): Wire Ampacity Size Table](https://www.encorewire.com/products/tools-and-resources/calculators/wire-size-table.html)
- [City and County of Denver (Denver Residential Code 2021, adopting the 2021 IRC); viewer hosted by UpCodes: Chapter 36 Services: Denver Residential Code 2021 (based on the 2021 International Residential Code), Section E3603.1.1 Ungrounded Service Conductors](https://up.codes/viewer/denver/irc-2021/chapter/36/services)
- [Cerrowire Ampacity Chart (ampacities based on the 2017 NEC Table 310.16)](https://www.cerrowire.com/wp-content/uploads/2021/04/Cerrowire_Ampacity_Chart_210405.pdf)
- [IAEI (International Association of Electrical Inspectors), IAEI Magazine, Focus on the Code: Are there any practical guidelines available to installers and the enforcement community with regards to continuous loads?](https://iaeimagazine.org/columns/focus-on-the-code/are-there-any-practical-guidelines-available-to-installers-and-the-enforement-community-with-regards-to-continuous-loads/)
- [Mesa County (Colorado) Community Development Department, Building Division: Homeowner's Wiring Guideline 2020 (Administrative Review Application Process), effective March 1, 2021](https://www.mesacounty.us/sites/default/files/2022-12/residential-wiring-guideline-2020-nec-effective-3-1-2021.pdf)