# What Size Wire for a 30 Amp Circuit

A 30 amp circuit takes 10 AWG copper, the largest breaker the code allows on that size, or 8 AWG aluminum. That covers the usual clothes dryer, an electric water heater, a small air conditioner or a 30 amp RV hookup, as long as the run is not long. The calculator starts at 30 amps and 240 volts; enter how far the load is from the panel.

Reviewed by FigureYard editorial team · Updated October 13, 2026 · 7 sources

*Interactive calculator on the page (inputs: The wire feeds; Load current; Circuit voltage; One-way distance; Conductor; Wire type; Runs for 3 hours or more at a time; Circuit; Allowed voltage drop (%)). The results below are for its default inputs.*

**Wire size**

**10 AWG** copper

- Current the wire must carry: **30.0** A
- Rated for: **30** A
- Voltage drop: **1.24** %
- Longest run within 3%: **97** ft

Each copper size for this circuit

| Size | Rated | Drop | Fits |
| --- | --- | --- | --- |
| 14 AWG | 15 A | 3.14% | Too small for the current |
| 12 AWG | 20 A | 1.98% | Too small for the current |
| 10 AWG | 30 A | 1.24% | Yes |
| 8 AWG | 40 A | 0.78% | Yes |
| 6 AWG | 55 A | 0.49% | Yes |

If the appliance runs for hours at full power, a water heater for example, the circuit has to be sized for more than its nameplate current, and the calculator handles that when you mark it as continuous.

## How to use this calculator

1. Enter 30 amps for a circuit sized to its breaker, or the appliance's nameplate current if you are working out what breaker it needs.
2. Pick 240 volts for a dryer, a water heater or an air conditioner, and 120 volts for the common TT-30 RV receptacle.
3. Enter the one-way distance from the panel to the appliance or the pedestal.
4. Mark the load as continuous when it runs at full current for 3 hours or more: the wire must then carry 125 percent of it.

## Worked examples

### A clothes dryer in the laundry room

Load current: 30 A · Circuit voltage: 240 V · One-way distance: 35 ft

- Wire size: 10 AWG copper
- Current the wire must carry: 30.0 A
- Rated for: 30 A
- Voltage drop: 1.09%
- Longest run within 3%: 97 ft

### An electric water heater in the basement

Load current: 18.75 A · Circuit voltage: 240 V · One-way distance: 25 ft · Runs for 3 hours or more at a time: Yes, a continuous load

- Wire size: 10 AWG copper
- Current the wire must carry: 23.4 A
- Rated for: 30 A
- Voltage drop: 0.48%
- Longest run within 3%: 155 ft

### A TT-30 RV receptacle by the driveway

Load current: 30 A · Circuit voltage: 120 V · One-way distance: 90 ft

- Wire size: 6 AWG copper
- Current the wire must carry: 30.0 A
- Rated for: 55 A
- Voltage drop: 2.21%
- Longest run within 3%: 122 ft

## Wire size for a 30 amp circuit by one-way distance

| One-way distance | 240 V, Copper | 120 V, Copper | 240 V, Aluminum |
| --- | --- | --- | --- |
| 25 ft | 10 AWG | 10 AWG | 8 AWG |
| 50 ft | 10 AWG | 8 AWG | 8 AWG |
| 75 ft | 10 AWG | 8 AWG | 8 AWG |
| 100 ft | 8 AWG | 6 AWG | 6 AWG |
| 150 ft | 8 AWG | 4 AWG | 4 AWG |

Each cell: the smallest size that carries the current within the usual branch-circuit drop. A 120 volt circuit loses twice the percentage of a 240 volt one over the same wire, so it needs a thicker size sooner.

## Why 10 AWG is the answer for most 30 amp circuits

The code caps the breaker on 10 AWG copper at 30 amps, the same as its ampacity in the cable column, so the size and the circuit match exactly. 12 AWG is limited to 20 amps and cannot be used, even for a short run. Aluminum is capped lower: 10 AWG aluminum may carry only 25 amps, which is why an aluminum 30 amp circuit needs 8 AWG.

## Dryers, water heaters and RV hookups

A dryer circuit needs a neutral for the drum motor and controls, so it is run in 10/3 cable with a ground. A water heater uses only the two hots and a ground, and because it heats for long stretches it counts as continuous: its nameplate current times 125 percent must fit the wire. A TT-30 RV receptacle is 120 volts, and a camper at the far end of a driveway often needs 8 AWG or more to keep the air conditioner from tripping on low voltage. The table shows how quickly the 120 volt column grows.

## Before you buy the cable

Measure along the real route, add the drops up and down the walls, and use the one-way length in the calculator. The breaker stays at 30 amps when you go up a wire size for distance, and the [amps calculator](https://figureyard.com/energy/amp-calculator/) turns an appliance's watts into the current to enter.

## Common questions

### What size wire for a 30 amp dryer?

10 AWG copper in 10/3 cable with a ground, which is rated 30 amps and is the largest size the code allows on that breaker. A very long run may call for 8 AWG.

### Can I use 12 gauge wire on a 30 amp breaker?

No. 12 AWG copper is limited to a breaker of 20 amps. A 30 amp breaker needs 10 AWG copper or 8 AWG aluminum at least.

### What size aluminum wire for 30 amps?

8 AWG aluminum, rated 40 amps. 10 AWG aluminum is limited to a breaker of 25 amps, so it is too small for a 30 amp circuit.

### Is 10 gauge wire good for 30 amps at 100 feet?

Not at the full 30 amps. Over that distance 10 AWG loses more than 3 percent even at 240 volts, so 8 AWG is the size to use, and at 120 volts the drop doubles and calls for 6 AWG. The table shows each step.

## Related calculators

- [Wire Size Calculator](https://figureyard.com/energy/wire-size-calculator/)
- [Voltage Drop Calculator](https://figureyard.com/energy/voltage-drop-calculator/)
- [What Size Wire for a 20 Amp Circuit](https://figureyard.com/energy/wire-size-for-20-amp/)
- [What Size Wire for a 50 Amp Circuit](https://figureyard.com/energy/wire-size-for-50-amp/)
- [Amp Calculator](https://figureyard.com/energy/amp-calculator/)

Reviewed by FigureYard editorial team on 2026-10-13. Formulas are tested against published values, and material figures come from the sources below. [How we build our calculators](https://figureyard.com/editorial-policy/).

## Sources

- [Michigan State University Electrical Tech Note 227: Sizing Conductors to Minimize Voltage Drop (Table 227.1, dc resistance at 75 °C)](https://www.maec.msu.edu/download_file/view/147/303)
- [Cerrowire Voltage Drop Table (rev. 09/2018)](https://www.cerrowire.com/wp-content/uploads/2018/09/Cerrowire_Voltage-Drop_210521.pdf)
- [Electrical License Renewal (reproduces NEC 210.19(A)(1) text): 210.19(A)(1) Branch Circuits.](https://www.electricallicenserenewal.com/Electrical-Continuing-Education-Courses/NEC-Content.php?sectionID=818)
- [Encore Wire (Prysmian): Wire Ampacity Size Table](https://www.encorewire.com/products/tools-and-resources/calculators/wire-size-table.html)
- [City and County of Denver (Denver Residential Code 2021, adopting the 2021 IRC); viewer hosted by UpCodes: Chapter 36 Services: Denver Residential Code 2021 (based on the 2021 International Residential Code), Section E3603.1.1 Ungrounded Service Conductors](https://up.codes/viewer/denver/irc-2021/chapter/36/services)
- [Cerrowire Ampacity Chart (ampacities based on the 2017 NEC Table 310.16)](https://www.cerrowire.com/wp-content/uploads/2021/04/Cerrowire_Ampacity_Chart_210405.pdf)
- [IAEI (International Association of Electrical Inspectors), IAEI Magazine, Focus on the Code: Are there any practical guidelines available to installers and the enforcement community with regards to continuous loads?](https://iaeimagazine.org/columns/focus-on-the-code/are-there-any-practical-guidelines-available-to-installers-and-the-enforement-community-with-regards-to-continuous-loads/)