title: "What Size Wire for 60 Amps? Subpanel, EV, Hot Tub | FigureYard"
description: "Wire size for a 60 amp breaker: 4 AWG copper NM-B, 6 AWG THHN in conduit or 4 AWG aluminum, for subpanels, car chargers and hot tubs."
url: https://figureyard.com/energy/wire-size-for-60-amp/
image: https://figureyard.com/og/energy/wire-size-for-60-amp.png
---

[Electrical, Heating & Insulation](https://figureyard.com/energy/)

# What Size Wire for a 60 Amp Circuit

A 60 amp circuit needs 6 AWG copper as single THHN wires in conduit, 4 AWG copper in NM-B cable, or 4 AWG aluminum. The cable answer is a size bigger because NM-B is rated from the code's lowest temperature column, where 6 AWG falls just short of sixty. The calculator is set to a 60 amp, 240 volt circuit in conduit; change the wire type, the metal and the distance to match your job.

Reviewed by FigureYard editorial team · Updated October 13, 2026 · 6 sources

*Interactive calculator on the page (inputs: The wire feeds; Load current; Circuit voltage; One-way distance; Conductor; Wire type; Runs for 3 hours or more at a time; Circuit; Allowed voltage drop (%)). The results below are for its default inputs.*

**Wire size**

**6 AWG** copper

- Current the wire must carry: **60.0** A
- Rated for: **65** A
- Voltage drop: **1.47** %
- Longest run within 3%: **122** ft

Each copper size for this circuit

| Size | Rated | Drop | Fits |
| --- | --- | --- | --- |
| 10 AWG | 30 A | 3.72% | Too small for the current |
| 8 AWG | 50 A | 2.33% | Too small for the current |
| 6 AWG | 65 A | 1.47% | Yes |
| 4 AWG | 85 A | 0.92% | Yes |
| 3 AWG | 100 A | 0.74% | Yes |

Sixty amps is a common size for a small subpanel in a garage or a workshop, a hot tub, a tankless water heater, and a car charger that delivers forty-eight amps.

## How to use this calculator

1. Keep 60 amps for a feeder or circuit sized to its breaker.
2. Choose NM-B cable for a run inside the walls of the house, or THHN wires for conduit, which is what most subpanel feeders and outdoor runs use.
3. Enter the one-way distance. For a detached garage, measure to the subpanel, not to the far end of the building.
4. Mark a car charger as continuous: its circuit is sized for 125 percent of the charging current.

## Worked examples

### A garage subpanel fed through the attic

Load current: 60 A · Circuit voltage: 240 V · One-way distance: 70 ft · Wire type: NM-B or UF-B cable (60 °C)

- Wire size: 4 AWG copper
- Current the wire must carry: 60.0 A
- Rated for: 70 A
- Voltage drop: 1.08%
- Longest run within 3%: 195 ft

### A hot tub on the patio

Load current: 60 A · Circuit voltage: 240 V · One-way distance: 45 ft · Wire type: THHN/THWN wires in conduit (75 °C)

- Wire size: 6 AWG copper
- Current the wire must carry: 60.0 A
- Rated for: 65 A
- Voltage drop: 1.10%
- Longest run within 3%: 122 ft

### A car charger at its highest setting

Load current: 48 A · Circuit voltage: 240 V · One-way distance: 55 ft · Wire type: THHN/THWN wires in conduit (75 °C) · Runs for 3 hours or more at a time: Yes, a continuous load

- Wire size: 6 AWG copper
- Current the wire must carry: 60.0 A
- Rated for: 65 A
- Voltage drop: 1.08%
- Longest run within 3%: 153 ft

### An aluminum feeder to a workshop

Load current: 60 A · Circuit voltage: 240 V · One-way distance: 180 ft · Conductor: Aluminum

- Wire size: 2 AWG aluminum
- Current the wire must carry: 60.0 A
- Rated for: 90 A
- Voltage drop: 2.87%
- Longest run within 3%: 188 ft

## Wire size for a 60 amp, 240 volt circuit by one-way distance

| One-way distance | Copper, THHN/THWN wires in conduit (75 °C) | Copper, NM-B or UF-B cable (60 °C) | Aluminum |
| --- | --- | --- | --- |
| 25 ft | 6 AWG | 4 AWG | 4 AWG |
| 50 ft | 6 AWG | 4 AWG | 4 AWG |
| 100 ft | 6 AWG | 4 AWG | 4 AWG |
| 150 ft | 4 AWG | 4 AWG | 2 AWG |
| 200 ft | 3 AWG | 3 AWG | 1 AWG |

Each cell: the smallest size that carries sixty amps within the usual branch-circuit drop, from the base ampacity table.

## Cable or conduit: 4 AWG or 6 AWG

In the lowest temperature column, which NM-B cable must use, 6 AWG copper is rated 55 amps and 4 AWG 70 amps, so a 60 amp breaker on cable needs 4 AWG. Single THHN or THWN wires may use the next column, where 6 AWG carries 65 amps, when the breaker and the equipment terminals are rated for it; subpanels and car chargers generally are. Aluminum 4 AWG is rated 65 amps in the same column, and aluminum is the usual choice for a long feeder because the larger sizes cost far less than copper.

## A subpanel feeder needs four wires

A subpanel takes two hots, a neutral and a separate ground, and in the subpanel the neutrals and grounds stay on separate bars. A detached building also needs its own grounding electrode. Voltage drop on a feeder is usually held tighter than on a branch circuit, about 2 percent, so the remaining 3 percent is left for the circuits beyond it: open More options and set the allowed drop to check a long feeder that way.

## Hot tubs and car chargers

Hot tubs are fed through a GFCI disconnect within sight of the tub, and the manufacturer's manual names the breaker; many need sixty amps, some fifty. A car charger running at forty-eight amps is a continuous load: the wire must carry 125 percent of that, which is exactly sixty. Check the [50 amp wire guide](https://figureyard.com/energy/wire-size-for-50-amp/) if your charger runs at forty.

## Common questions

### Is 6 gauge wire good for 60 amps?

As single copper THHN or THWN wires with terminals rated for the higher column, yes: 6 AWG carries 65 amps. In NM-B cable it is rated 55 amps, so a 60 amp breaker on cable needs 4 AWG.

### What size aluminum wire for a 60 amp subpanel?

4 AWG aluminum, rated 65 amps, for a short feeder. On a long run to a detached building, voltage drop often calls for 2 AWG; the table shows where.

### What wire do I need for a 48 amp car charger?

A charger that delivers forty-eight amps is continuous, so its circuit is a 60 amp one: 6 AWG copper THHN in conduit, or 4 AWG copper NM-B cable, on a short run.

### Does a 60 amp subpanel need a ground wire?

Yes. A subpanel is fed with two hots, a neutral and an equipment ground, and its neutral bar is kept separate from the ground bar.

## Related calculators

- [Wire Size Calculator](https://figureyard.com/energy/wire-size-calculator/)
- [Voltage Drop Calculator](https://figureyard.com/energy/voltage-drop-calculator/)
- [What Size Wire for a 50 Amp Circuit](https://figureyard.com/energy/wire-size-for-50-amp/)
- [Wire Size for a 100 Amp Subpanel](https://figureyard.com/energy/wire-size-for-100-amp-subpanel/)
- [Amp Calculator](https://figureyard.com/energy/amp-calculator/)

Reviewed by FigureYard editorial team on 2026-10-13. Formulas are tested against published values, and material figures come from the sources below. [How we build our calculators](https://figureyard.com/editorial-policy/).

## Sources

- [Michigan State University Electrical Tech Note 227: Sizing Conductors to Minimize Voltage Drop (Table 227.1, dc resistance at 75 °C)](https://www.maec.msu.edu/download_file/view/147/303)
- [Cerrowire Voltage Drop Table (rev. 09/2018)](https://www.cerrowire.com/wp-content/uploads/2018/09/Cerrowire_Voltage-Drop_210521.pdf)
- [Electrical License Renewal (reproduces NEC 210.19(A)(1) text): 210.19(A)(1) Branch Circuits.](https://www.electricallicenserenewal.com/Electrical-Continuing-Education-Courses/NEC-Content.php?sectionID=818)
- [Encore Wire (Prysmian): Wire Ampacity Size Table](https://www.encorewire.com/products/tools-and-resources/calculators/wire-size-table.html)
- [City and County of Denver (Denver Residential Code 2021, adopting the 2021 IRC); viewer hosted by UpCodes: Chapter 36 Services: Denver Residential Code 2021 (based on the 2021 International Residential Code), Section E3603.1.1 Ungrounded Service Conductors](https://up.codes/viewer/denver/irc-2021/chapter/36/services)
- [Cerrowire Ampacity Chart (ampacities based on the 2017 NEC Table 310.16)](https://www.cerrowire.com/wp-content/uploads/2021/04/Cerrowire_Ampacity_Chart_210405.pdf)