# AWG Wire Resistance Chart, with Voltage Drop Distances

Every voltage drop calculation starts from one number: the resistance of the wire. This chart lists it for stranded copper and aluminum conductors, from the thin gauges used for low-voltage lighting up to the large sizes used for feeders.

Checked by FigureYard editorial team · Updated October 12, 2026 · 4 sources

The second and third tables turn those resistances into something you can use on site: the longest one-way run for each size before the drop passes the usual branch-circuit limit. For your own voltage, load and distance, use the [voltage drop calculator](https://figureyard.com/energy/voltage-drop-calculator/).

## Resistance by wire size

Each step down in AWG number is a thicker wire with less resistance. Aluminum conducts less well than copper, so an aluminum wire has more resistance than a copper one of the same size.

*DC resistance of stranded conductors at the standard rating temperature*

| Size | Copper, ohms per 1,000 ft | Copper, ohms per km | Aluminum, ohms per 1,000 ft | Aluminum, ohms per km | Source |
| --- | --- | --- | --- | --- | --- |
| 18 AWG | 7.95 | 26.1 | – | – | [MSU tech note](https://www.maec.msu.edu/download_file/view/147/303) |
| 16 AWG | 4.99 | 16.4 | – | – | [MSU tech note](https://www.maec.msu.edu/download_file/view/147/303) |
| 14 AWG | 3.14 | 10.3 | – | – | [MSU tech note](https://www.maec.msu.edu/download_file/view/147/303) |
| 12 AWG | 1.98 | 6.50 | 3.25 | 10.6 | [MSU tech note](https://www.maec.msu.edu/download_file/view/147/303) |
| 10 AWG | 1.24 | 4.07 | 2.04 | 6.67 | [MSU tech note](https://www.maec.msu.edu/download_file/view/147/303) |
| 8 AWG | 0.778 | 2.55 | 1.28 | 4.20 | [MSU tech note](https://www.maec.msu.edu/download_file/view/147/303) |
| 6 AWG | 0.491 | 1.61 | 0.808 | 2.65 | [MSU tech note](https://www.maec.msu.edu/download_file/view/147/303) |
| 4 AWG | 0.308 | 1.01 | 0.508 | 1.67 | [MSU tech note](https://www.maec.msu.edu/download_file/view/147/303) |
| 3 AWG | 0.245 | 0.802 | 0.403 | 1.32 | [MSU tech note](https://www.maec.msu.edu/download_file/view/147/303) |
| 2 AWG | 0.194 | 0.634 | 0.319 | 1.05 | [MSU tech note](https://www.maec.msu.edu/download_file/view/147/303) |
| 1 AWG | 0.154 | 0.505 | 0.253 | 0.829 | [MSU tech note](https://www.maec.msu.edu/download_file/view/147/303) |
| 1/0 AWG | 0.122 | 0.399 | 0.201 | 0.660 | [MSU tech note](https://www.maec.msu.edu/download_file/view/147/303) |
| 2/0 AWG | 0.0967 | 0.317 | 0.159 | 0.523 | [MSU tech note](https://www.maec.msu.edu/download_file/view/147/303) |
| 3/0 AWG | 0.0766 | 0.251 | 0.126 | 0.413 | [MSU tech note](https://www.maec.msu.edu/download_file/view/147/303) |
| 4/0 AWG | 0.0608 | 0.200 | 0.100 | 0.328 | [MSU tech note](https://www.maec.msu.edu/download_file/view/147/303) |

Values are for uncoated stranded conductors at 75 °C, as published in a university extension tech note. A dash means the table gives no aluminum value for that size.

## How far each copper size can run

These distances hold the drop to 3 percent, the limit most wire sizing tables use for a branch circuit. Double the voltage and a size can run twice as far at the same current; double the current and it can run only half as far.

*Longest one-way run in feet for copper wire within the branch-circuit limit*

| Size | 120 V, 15 A | 120 V, 20 A | 240 V, 20 A | 240 V, 30 A | 240 V, 50 A |
| --- | --- | --- | --- | --- | --- |
| 14 AWG | 38 | 29 | 57 | 38 | 23 |
| 12 AWG | 61 | 45 | 91 | 61 | 36 |
| 10 AWG | 97 | 73 | 145 | 97 | 58 |
| 8 AWG | 154 | 116 | 231 | 154 | 93 |
| 6 AWG | 244 | 183 | 367 | 244 | 147 |
| 4 AWG | 390 | 292 | 584 | 390 | 234 |
| 3 AWG | 490 | 367 | 735 | 490 | 294 |
| 2 AWG | 619 | 464 | 928 | 619 | 371 |
| 1 AWG | 779 | 584 | 1,169 | 779 | 468 |
| 1/0 AWG | 984 | 738 | 1,475 | 984 | 590 |
| 2/0 AWG | 1,241 | 931 | 1,861 | 1,241 | 745 |
| 3/0 AWG | 1,567 | 1,175 | 2,350 | 1,567 | 940 |
| 4/0 AWG | 1,974 | 1,480 | 2,961 | 1,974 | 1,184 |

Our arithmetic from the copper resistances above: single-phase or DC, current out and back, voltage drop held to 3 percent. These distances check voltage drop only, not whether the wire is rated for the current.

## How far each aluminum size can run

Aluminum is common for large feeders and service conductors because it is lighter and cheaper, and it is sized up to make up for its higher resistance.

*Longest one-way run in feet for aluminum wire within the branch-circuit limit*

| Size | 120 V, 15 A | 120 V, 20 A | 240 V, 20 A | 240 V, 30 A | 240 V, 50 A |
| --- | --- | --- | --- | --- | --- |
| 12 AWG | 37 | 28 | 55 | 37 | 22 |
| 10 AWG | 59 | 44 | 88 | 59 | 35 |
| 8 AWG | 94 | 70 | 141 | 94 | 56 |
| 6 AWG | 149 | 111 | 223 | 149 | 89 |
| 4 AWG | 236 | 177 | 354 | 236 | 142 |
| 3 AWG | 298 | 223 | 447 | 298 | 179 |
| 2 AWG | 376 | 282 | 564 | 376 | 226 |
| 1 AWG | 474 | 356 | 711 | 474 | 285 |
| 1/0 AWG | 597 | 448 | 896 | 597 | 358 |
| 2/0 AWG | 755 | 566 | 1,132 | 755 | 453 |
| 3/0 AWG | 952 | 714 | 1,429 | 952 | 571 |
| 4/0 AWG | 1,200 | 900 | 1,800 | 1,200 | 720 |

Our arithmetic from the aluminum resistances above, on the same basis as the copper table.

## Using these figures

- The resistances are for the conductor temperature building wire is normally rated at. A cooler wire has slightly less resistance, so the figures err on the safe side for most runs.
- Voltage drop is one of two checks. The electrical code also sets the smallest wire for each breaker and load, and the larger of the two answers wins.
- On AC circuits these figures leave out the small effect of inductance, which matters mainly for very large conductors and long feeders.
- The common targets are 3 percent on a branch circuit, 2 percent on a feeder and 5 percent in total from the source to the farthest load.

## Common questions

### What is the resistance of 12 AWG copper wire?

Stranded 12 AWG copper is 1.98 ohms per 1,000 ft at 75 °C. A run out and back counts the length of both conductors.

### How far can I run 12 AWG wire on a 20 amp circuit?

About 45 ft one way on a 120 V circuit, or 91 ft one way on a 240 V circuit, with the full 20 amps the breaker allows and the drop held to 3 percent. A lighter load can run farther; the voltage drop calculator works it out for your exact load.

### Why does aluminum wire need to be a larger size?

Aluminum has more resistance than copper of the same size: 12 AWG aluminum is 3.25 ohms per 1,000 ft against 1.98 ohms per 1,000 ft for copper. A larger size brings the resistance, and the voltage drop, back down.

## Using these figures

You are welcome to cite the tables on this page. Please link to this page as the source, and check the maker's current data sheet before you rely on a single figure.

## Calculators

- [Voltage Drop Calculator](https://figureyard.com/energy/voltage-drop-calculator/)
- [Electricity Cost Calculator](https://figureyard.com/energy/electricity-cost-calculator/)

Checked by FigureYard editorial team on 2026-10-09. Every figure is copied from the published source linked beside it. [How we check data](https://figureyard.com/editorial-policy/).

## Sources

- [Michigan State University Electrical Tech Note 227: Sizing Conductors to Minimize Voltage Drop (Table 227.1)](https://www.maec.msu.edu/download_file/view/147/303)
- [Cerrowire Voltage Drop Table (rev. 09/2018)](https://www.cerrowire.com/wp-content/uploads/2018/09/Cerrowire_Voltage-Drop_210521.pdf)
- [Washington State Energy Code, WAC 51-11C-40511 (Section C405.11 Voltage drop)](https://lawfilesext.leg.wa.gov/law/WACArchive/2023/htm/WAC%20%2051%20%20TITLE/WAC%20%2051%20-%2011C%20CHAPTER/WAC%20%2051%20-%2011C-40511.htm)
- [Encore Wire (Prysmian): Wire Ampacity Size Table](https://www.encorewire.com/products/tools-and-resources/calculators/wire-size-table.html)