The second and third tables turn those resistances into something you can use on site: the longest one-way run for each size before the drop passes the usual branch-circuit limit. For your own voltage, load and distance, use the voltage drop calculator.
Resistance by wire size
Each step down in AWG number is a thicker wire with less resistance. Aluminum conducts less well than copper, so an aluminum wire has more resistance than a copper one of the same size.
| Size | Copper, ohms per 1,000 ft | Copper, ohms per km | Aluminum, ohms per 1,000 ft | Aluminum, ohms per km | Source |
|---|---|---|---|---|---|
| 18 AWG | 7.95 | 26.1 | – | – | MSU tech note |
| 16 AWG | 4.99 | 16.4 | – | – | MSU tech note |
| 14 AWG | 3.14 | 10.3 | – | – | MSU tech note |
| 12 AWG | 1.98 | 6.50 | 3.25 | 10.6 | MSU tech note |
| 10 AWG | 1.24 | 4.07 | 2.04 | 6.67 | MSU tech note |
| 8 AWG | 0.778 | 2.55 | 1.28 | 4.20 | MSU tech note |
| 6 AWG | 0.491 | 1.61 | 0.808 | 2.65 | MSU tech note |
| 4 AWG | 0.308 | 1.01 | 0.508 | 1.67 | MSU tech note |
| 3 AWG | 0.245 | 0.802 | 0.403 | 1.32 | MSU tech note |
| 2 AWG | 0.194 | 0.634 | 0.319 | 1.05 | MSU tech note |
| 1 AWG | 0.154 | 0.505 | 0.253 | 0.829 | MSU tech note |
| 1/0 AWG | 0.122 | 0.399 | 0.201 | 0.660 | MSU tech note |
| 2/0 AWG | 0.0967 | 0.317 | 0.159 | 0.523 | MSU tech note |
| 3/0 AWG | 0.0766 | 0.251 | 0.126 | 0.413 | MSU tech note |
| 4/0 AWG | 0.0608 | 0.200 | 0.100 | 0.328 | MSU tech note |
Values are for uncoated stranded conductors at 75 °C, as published in a university extension tech note. A dash means the table gives no aluminum value for that size.
How far each copper size can run
These distances hold the drop to 3 percent, the limit most wire sizing tables use for a branch circuit. Double the voltage and a size can run twice as far at the same current; double the current and it can run only half as far.
| Size | 120 V, 15 A | 120 V, 20 A | 240 V, 20 A | 240 V, 30 A | 240 V, 50 A |
|---|---|---|---|---|---|
| 14 AWG | 38 | 29 | 57 | 38 | 23 |
| 12 AWG | 61 | 45 | 91 | 61 | 36 |
| 10 AWG | 97 | 73 | 145 | 97 | 58 |
| 8 AWG | 154 | 116 | 231 | 154 | 93 |
| 6 AWG | 244 | 183 | 367 | 244 | 147 |
| 4 AWG | 390 | 292 | 584 | 390 | 234 |
| 3 AWG | 490 | 367 | 735 | 490 | 294 |
| 2 AWG | 619 | 464 | 928 | 619 | 371 |
| 1 AWG | 779 | 584 | 1,169 | 779 | 468 |
| 1/0 AWG | 984 | 738 | 1,475 | 984 | 590 |
| 2/0 AWG | 1,241 | 931 | 1,861 | 1,241 | 745 |
| 3/0 AWG | 1,567 | 1,175 | 2,350 | 1,567 | 940 |
| 4/0 AWG | 1,974 | 1,480 | 2,961 | 1,974 | 1,184 |
Our arithmetic from the copper resistances above: single-phase or DC, current out and back, voltage drop held to 3 percent. These distances check voltage drop only, not whether the wire is rated for the current.
How far each aluminum size can run
Aluminum is common for large feeders and service conductors because it is lighter and cheaper, and it is sized up to make up for its higher resistance.
| Size | 120 V, 15 A | 120 V, 20 A | 240 V, 20 A | 240 V, 30 A | 240 V, 50 A |
|---|---|---|---|---|---|
| 12 AWG | 37 | 28 | 55 | 37 | 22 |
| 10 AWG | 59 | 44 | 88 | 59 | 35 |
| 8 AWG | 94 | 70 | 141 | 94 | 56 |
| 6 AWG | 149 | 111 | 223 | 149 | 89 |
| 4 AWG | 236 | 177 | 354 | 236 | 142 |
| 3 AWG | 298 | 223 | 447 | 298 | 179 |
| 2 AWG | 376 | 282 | 564 | 376 | 226 |
| 1 AWG | 474 | 356 | 711 | 474 | 285 |
| 1/0 AWG | 597 | 448 | 896 | 597 | 358 |
| 2/0 AWG | 755 | 566 | 1,132 | 755 | 453 |
| 3/0 AWG | 952 | 714 | 1,429 | 952 | 571 |
| 4/0 AWG | 1,200 | 900 | 1,800 | 1,200 | 720 |
Our arithmetic from the aluminum resistances above, on the same basis as the copper table.
Using these figures
- The resistances are for the conductor temperature building wire is normally rated at. A cooler wire has slightly less resistance, so the figures err on the safe side for most runs.
- Voltage drop is one of two checks. The electrical code also sets the smallest wire for each breaker and load, and the larger of the two answers wins.
- On AC circuits these figures leave out the small effect of inductance, which matters mainly for very large conductors and long feeders.
- The common targets are 3 percent on a branch circuit, 2 percent on a feeder and 5 percent in total from the source to the farthest load.
Common questions
What is the resistance of 12 AWG copper wire?
Stranded 12 AWG copper is 1.98 ohms per 1,000 ft at 75 °C. A run out and back counts the length of both conductors.
How far can I run 12 AWG wire on a 20 amp circuit?
At the usual branch-circuit limit, the copper table above gives the distance for a fully loaded circuit at the common household voltages. A lighter load can run farther; the voltage drop calculator works it out for your exact load.
Why does aluminum wire need to be a larger size?
Aluminum has more resistance than copper of the same size: 12 AWG aluminum is 3.25 ohms per 1,000 ft against 1.98 ohms per 1,000 ft for copper. A larger size brings the resistance, and the voltage drop, back down.
Using these figures
You are welcome to cite the tables on this page. Please link to this page as the source, and check the maker's current data sheet before you rely on a single figure.