What Size Wire for a 20 Amp Circuit

A 20 amp circuit needs 12 AWG copper: the code lets that size carry a breaker of 20 amps and no more, and 14 AWG is never allowed on it. The catch is distance. At 120 volts a fully loaded 20 amp circuit loses voltage fast, so a garage, a shed or a backyard receptacle a long way from the panel often needs 10 AWG instead.

Reviewed by FigureYard editorial teamUpdated October 13, 20266 sources

Your measurements

Remembered on this device
A
V
Conductor
More options
%
Wire size
12 AWGcopper
  • Current the wire must carry: 20.0 A
  • Rated for: 20 A
  • Voltage drop: 2.64%
  • Longest run within 3%: 45 ft
Each copper size for this circuit
SizeRatedDropFits
14 AWG15 A4.19%Too small for the current
12 AWG20 A2.64%Yes
10 AWG30 A1.65%Yes
8 AWG40 A1.04%Yes

12 AWG NM-B cable (60 °C column) is the smallest size here; the current sets it. This uses the base table: hot attics, more than three current-carrying wires together, and the terminals on your breaker and devices can call for a larger size. Have an electrician or your inspector confirm the circuit.

The calculator is preset to a 20 amp, 120 volt circuit. Type the one-way distance from the panel and it tells you whether 12 AWG still keeps the drop in check, or where you should go up a size.

How to use this calculator

  1. Leave the current at 20 amps for a general receptacle or lighting circuit: size the wire for the breaker, not for what you plan to plug in today.
  2. Enter the distance one way, measured along the path the cable will take, through the attic or along the joists, not in a straight line.
  3. Copper is the norm for circuits this small. Aluminum branch wiring is rare in new homes and needs devices marked for it.
  4. A dedicated 240 volt circuit of this size, for a small heater or a compressor, loses half the percentage: switch the voltage and compare.

Worked examples

Kitchen countertop receptacles

Load current: 20 A · Circuit voltage: 120 V · One-way distance: 35 ft

Wire size
12 AWG copper
Current the wire must carry
20.0 A
Rated for
20 A
Voltage drop
2.31%
Longest run within 3%
45 ft

A detached garage receptacle

Load current: 20 A · Circuit voltage: 120 V · One-way distance: 110 ft

Wire size
8 AWG copper
Current the wire must carry
20.0 A
Rated for
40 A
Voltage drop
2.85%
Longest run within 3%
116 ft

A baseboard heater on its own circuit

Load current: 16 A · Circuit voltage: 240 V · One-way distance: 60 ft · Runs for 3 hours or more at a time: Yes, a continuous load

Wire size
12 AWG copper
Current the wire must carry
20.0 A
Rated for
20 A
Voltage drop
1.58%
Longest run within 3%
114 ft

Wire size for a 20 amp circuit by one-way distance

One-way distance120 V, Copper240 V, Copper120 V, Aluminum
25 ft12 AWG12 AWG10 AWG
50 ft10 AWG12 AWG8 AWG
75 ft8 AWG12 AWG6 AWG
100 ft8 AWG10 AWG6 AWG
150 ft6 AWG8 AWG4 AWG

Each cell: the smallest size that carries the full current within the usual branch-circuit drop. Copper in NM-B cable; at this size the cable type does not change the answer.

Why 14 AWG cannot go on a 20 amp breaker

The ampacity table alone would let 14 AWG copper carry a little more than its everyday rating, but the code adds a separate cap for the three smallest sizes: 15 amps on 14 AWG, 20 amps on 12 AWG and 30 amps on 10 AWG. That cap is why a white-jacketed 14/2 cable on a 20 amp breaker is one of the most common inspection failures, and why a yellow 12/2 cable is the usual sight in kitchens, bathrooms, laundry rooms and garages, where the code calls for 20 amp receptacle circuits.

Long runs at 120 volts

Voltage drop grows with current and length and shrinks with voltage. A branch circuit is commonly kept within 3 percent, and at 120 volts and the full 20 amps, 12 AWG crosses that line well before the end of a long backyard run. Lights dim when a saw starts, and a compressor may struggle. Moving up to 10 AWG for the long stretch costs little and keeps the circuit honest; the breaker stays at 20 amps. The table shows the size each distance needs, and the voltage drop calculator gives the exact percentage for your own load.

Thicker wire and the receptacle terminals

Standard receptacles and switches accept 12 AWG easily. 10 AWG is stiff and fills the box, so many electricians run 10 AWG to the first box and finish with a short 12 AWG pigtail, which is allowed because the breaker protects both. Check the box fill and the device's label before you push heavy wire onto its screws.

Common questions

Can I use 14 gauge wire on a 20 amp breaker?

No. 14 AWG copper is limited to a breaker of 15 amps, so a 20 amp circuit needs 12 AWG or thicker, however short the run.

Is 12 gauge wire good for 20 amps?

Yes, 12 AWG copper is the standard size: the code allows it on a breaker of 20 amps. On a long run voltage drop can call for 10 AWG; enter your distance above.

How far can you run 12 gauge wire on a 20 amp circuit?

It depends on the load and the drop you accept. At the full 20 amps and 120 volts, staying within 3 percent limits 12 AWG to a fairly short run; the calculator shows the longest run for your numbers in its result.

Can I put 10 gauge wire on a 20 amp breaker?

Yes. A wire may always be bigger than the breaker needs; it only must not be smaller. Thicker wire on the same breaker is the usual fix for a long run.