What Size Wire for a 30 Amp Circuit

A 30 amp circuit takes 10 AWG copper, the largest breaker the code allows on that size, or 8 AWG aluminum. That covers the usual clothes dryer, an electric water heater, a small air conditioner or a 30 amp RV hookup, as long as the run is not long. The calculator starts at 30 amps and 240 volts; enter how far the load is from the panel.

Reviewed by FigureYard editorial teamUpdated October 13, 20267 sources

Your measurements

Remembered on this device
A
V
Conductor
More options
%
Wire size
10 AWGcopper
  • Current the wire must carry: 30.0 A
  • Rated for: 30 A
  • Voltage drop: 1.24%
  • Longest run within 3%: 97 ft
Each copper size for this circuit
SizeRatedDropFits
14 AWG15 A3.14%Too small for the current
12 AWG20 A1.98%Too small for the current
10 AWG30 A1.24%Yes
8 AWG40 A0.78%Yes
6 AWG55 A0.49%Yes

10 AWG NM-B cable (60 °C column) is the smallest size here; the current sets it. This uses the base table: hot attics, more than three current-carrying wires together, and the terminals on your breaker and devices can call for a larger size. Have an electrician or your inspector confirm the circuit.

If the appliance runs for hours at full power, a water heater for example, the circuit has to be sized for more than its nameplate current, and the calculator handles that when you mark it as continuous.

How to use this calculator

  1. Enter 30 amps for a circuit sized to its breaker, or the appliance's nameplate current if you are working out what breaker it needs.
  2. Pick 240 volts for a dryer, a water heater or an air conditioner, and 120 volts for the common TT-30 RV receptacle.
  3. Enter the one-way distance from the panel to the appliance or the pedestal.
  4. Mark the load as continuous when it runs at full current for 3 hours or more: the wire must then carry 125 percent of it.

Worked examples

A clothes dryer in the laundry room

Load current: 30 A · Circuit voltage: 240 V · One-way distance: 35 ft

Wire size
10 AWG copper
Current the wire must carry
30.0 A
Rated for
30 A
Voltage drop
1.09%
Longest run within 3%
97 ft

An electric water heater in the basement

Load current: 18.75 A · Circuit voltage: 240 V · One-way distance: 25 ft · Runs for 3 hours or more at a time: Yes, a continuous load

Wire size
10 AWG copper
Current the wire must carry
23.4 A
Rated for
30 A
Voltage drop
0.48%
Longest run within 3%
155 ft

A TT-30 RV receptacle by the driveway

Load current: 30 A · Circuit voltage: 120 V · One-way distance: 90 ft

Wire size
6 AWG copper
Current the wire must carry
30.0 A
Rated for
55 A
Voltage drop
2.21%
Longest run within 3%
122 ft

Wire size for a 30 amp circuit by one-way distance

One-way distance240 V, Copper120 V, Copper240 V, Aluminum
25 ft10 AWG10 AWG8 AWG
50 ft10 AWG8 AWG8 AWG
75 ft10 AWG8 AWG8 AWG
100 ft8 AWG6 AWG6 AWG
150 ft8 AWG4 AWG4 AWG

Each cell: the smallest size that carries the current within the usual branch-circuit drop. A 120 volt circuit loses twice the percentage of a 240 volt one over the same wire, so it needs a thicker size sooner.

Why 10 AWG is the answer for most 30 amp circuits

The code caps the breaker on 10 AWG copper at 30 amps, the same as its ampacity in the cable column, so the size and the circuit match exactly. 12 AWG is limited to 20 amps and cannot be used, even for a short run. Aluminum is capped lower: 10 AWG aluminum may carry only 25 amps, which is why an aluminum 30 amp circuit needs 8 AWG.

Dryers, water heaters and RV hookups

A dryer circuit needs a neutral for the drum motor and controls, so it is run in 10/3 cable with a ground. A water heater uses only the two hots and a ground, and because it heats for long stretches it counts as continuous: its nameplate current times 125 percent must fit the wire. A TT-30 RV receptacle is 120 volts, and a camper at the far end of a driveway often needs 8 AWG or more to keep the air conditioner from tripping on low voltage. The table shows how quickly the 120 volt column grows.

Before you buy the cable

Measure along the real route, add the drops up and down the walls, and use the one-way length in the calculator. The breaker stays at 30 amps when you go up a wire size for distance, and the amps calculator turns an appliance's watts into the current to enter.

Common questions

What size wire for a 30 amp dryer?

10 AWG copper in 10/3 cable with a ground, which is rated 30 amps and is the largest size the code allows on that breaker. A very long run may call for 8 AWG.

Can I use 12 gauge wire on a 30 amp breaker?

No. 12 AWG copper is limited to a breaker of 20 amps. A 30 amp breaker needs 10 AWG copper or 8 AWG aluminum at least.

What size aluminum wire for 30 amps?

8 AWG aluminum, rated 40 amps. 10 AWG aluminum is limited to a breaker of 25 amps, so it is too small for a 30 amp circuit.

Is 10 gauge wire good for 30 amps at 100 feet?

Not at the full 30 amps. Over that distance 10 AWG loses more than 3 percent even at 240 volts, so 8 AWG is the size to use, and at 120 volts the drop doubles and calls for 6 AWG. The table shows each step.