What Size Wire for a 60 Amp Circuit

A 60 amp circuit needs 6 AWG copper as single THHN wires in conduit, 4 AWG copper in NM-B cable, or 4 AWG aluminum. The cable answer is a size bigger because NM-B is rated from the code's lowest temperature column, where 6 AWG falls just short of sixty. The calculator is set to a 60 amp, 240 volt circuit in conduit; change the wire type, the metal and the distance to match your job.

Reviewed by FigureYard editorial teamUpdated October 13, 20266 sources

Your measurements

Remembered on this device
A
V
Conductor
More options
%
Wire size
6 AWGcopper
  • Current the wire must carry: 60.0 A
  • Rated for: 65 A
  • Voltage drop: 1.47%
  • Longest run within 3%: 122 ft
Each copper size for this circuit
SizeRatedDropFits
10 AWG30 A3.72%Too small for the current
8 AWG50 A2.33%Too small for the current
6 AWG65 A1.47%Yes
4 AWG85 A0.92%Yes
3 AWG100 A0.74%Yes

6 AWG THHN/THWN copper (75 °C column) is the smallest size here; the current sets it. This uses the base table: hot attics, more than three current-carrying wires together, and the terminals on your breaker and devices can call for a larger size. Have an electrician or your inspector confirm the circuit.

Sixty amps is a common size for a small subpanel in a garage or a workshop, a hot tub, a tankless water heater, and a car charger that delivers forty-eight amps.

How to use this calculator

  1. Keep 60 amps for a feeder or circuit sized to its breaker.
  2. Choose NM-B cable for a run inside the walls of the house, or THHN wires for conduit, which is what most subpanel feeders and outdoor runs use.
  3. Enter the one-way distance. For a detached garage, measure to the subpanel, not to the far end of the building.
  4. Mark a car charger as continuous: its circuit is sized for 125 percent of the charging current.

Worked examples

A garage subpanel fed through the attic

Load current: 60 A · Circuit voltage: 240 V · One-way distance: 70 ft · Wire type: NM-B or UF-B cable (60 °C)

Wire size
4 AWG copper
Current the wire must carry
60.0 A
Rated for
70 A
Voltage drop
1.08%
Longest run within 3%
195 ft

A hot tub on the patio

Load current: 60 A · Circuit voltage: 240 V · One-way distance: 45 ft · Wire type: THHN/THWN wires in conduit (75 °C)

Wire size
6 AWG copper
Current the wire must carry
60.0 A
Rated for
65 A
Voltage drop
1.10%
Longest run within 3%
122 ft

A car charger at its highest setting

Load current: 48 A · Circuit voltage: 240 V · One-way distance: 55 ft · Wire type: THHN/THWN wires in conduit (75 °C) · Runs for 3 hours or more at a time: Yes, a continuous load

Wire size
6 AWG copper
Current the wire must carry
60.0 A
Rated for
65 A
Voltage drop
1.08%
Longest run within 3%
153 ft

An aluminum feeder to a workshop

Load current: 60 A · Circuit voltage: 240 V · One-way distance: 180 ft · Conductor: Aluminum

Wire size
2 AWG aluminum
Current the wire must carry
60.0 A
Rated for
90 A
Voltage drop
2.87%
Longest run within 3%
188 ft

Wire size for a 60 amp, 240 volt circuit by one-way distance

One-way distanceCopper, THHN/THWN wires in conduit (75 °C)Copper, NM-B or UF-B cable (60 °C)Aluminum
25 ft6 AWG4 AWG4 AWG
50 ft6 AWG4 AWG4 AWG
100 ft6 AWG4 AWG4 AWG
150 ft4 AWG4 AWG2 AWG
200 ft3 AWG3 AWG1 AWG

Each cell: the smallest size that carries sixty amps within the usual branch-circuit drop, from the base ampacity table.

Cable or conduit: 4 AWG or 6 AWG

In the lowest temperature column, which NM-B cable must use, 6 AWG copper is rated 55 amps and 4 AWG 70 amps, so a 60 amp breaker on cable needs 4 AWG. Single THHN or THWN wires may use the next column, where 6 AWG carries 65 amps, when the breaker and the equipment terminals are rated for it; subpanels and car chargers generally are. Aluminum 4 AWG is rated 65 amps in the same column, and aluminum is the usual choice for a long feeder because the larger sizes cost far less than copper.

A subpanel feeder needs four wires

A subpanel takes two hots, a neutral and a separate ground, and in the subpanel the neutrals and grounds stay on separate bars. A detached building also needs its own grounding electrode. Voltage drop on a feeder is usually held tighter than on a branch circuit, about 2 percent, so the remaining 3 percent is left for the circuits beyond it: open More options and set the allowed drop to check a long feeder that way.

Hot tubs and car chargers

Hot tubs are fed through a GFCI disconnect within sight of the tub, and the manufacturer's manual names the breaker; many need sixty amps, some fifty. A car charger running at forty-eight amps is a continuous load: the wire must carry 125 percent of that, which is exactly sixty. Check the 50 amp wire guide if your charger runs at forty.

Common questions

Is 6 gauge wire good for 60 amps?

As single copper THHN or THWN wires with terminals rated for the higher column, yes: 6 AWG carries 65 amps. In NM-B cable it is rated 55 amps, so a 60 amp breaker on cable needs 4 AWG.

What size aluminum wire for a 60 amp subpanel?

4 AWG aluminum, rated 65 amps, for a short feeder. On a long run to a detached building, voltage drop often calls for 2 AWG; the table shows where.

What wire do I need for a 48 amp car charger?

A charger that delivers forty-eight amps is continuous, so its circuit is a 60 amp one: 6 AWG copper THHN in conduit, or 4 AWG copper NM-B cable, on a short run.

Does a 60 amp subpanel need a ground wire?

Yes. A subpanel is fed with two hots, a neutral and an equipment ground, and its neutral bar is kept separate from the ground bar.