Wire Size for a 100 Amp Subpanel

A 100 amp subpanel is fed with 3 AWG copper or 1 AWG aluminum, both rated for exactly one hundred amps in the code's higher temperature column. That column applies to THHN or THWN wires in conduit and to SER cable when the breaker and the panel lugs are rated for it, which they usually are. The smaller sizes you may see quoted for a 100 amp house service do not apply here: that allowance is only for the service that feeds a whole home.

Reviewed by FigureYard editorial teamUpdated October 13, 20266 sources

Your measurements

Remembered on this device
A
V
Conductor
More options
%
Wire size
3 AWGcopper
  • Current the wire must carry: 100.0 A
  • Rated for: 100 A
  • Voltage drop: 1.23%
  • Longest run within 3%: 147 ft
Each copper size for this circuit
SizeRatedDropFits
8 AWG50 A3.89%Too small for the current
6 AWG65 A2.46%Too small for the current
4 AWG85 A1.54%Too small for the current
3 AWG100 A1.23%Yes
2 AWG115 A0.97%Yes
1 AWG130 A0.77%Yes

3 AWG THHN/THWN copper (75 °C column) is the smallest size here; the current sets it. This uses the base table: hot attics, more than three current-carrying wires together, and the terminals on your breaker and devices can call for a larger size. Have an electrician or your inspector confirm the circuit.

The calculator is preset to a 100 amp feeder at 240 volts in conduit. Enter the distance to the subpanel; a detached garage or barn at the far end of the yard often needs the next size up for voltage drop.

How to use this calculator

  1. Keep the current at 100 amps, the rating of the feeder breaker in the main panel.
  2. Choose copper or aluminum. Aluminum is by far the more common feeder at this size because it costs much less.
  3. Enter the one-way distance from the main panel to the subpanel along the trench or the conduit route.
  4. Open More options and set the allowed drop to 2 percent if you want to keep the feeder tight and leave room for the circuits beyond it.

Worked examples

A subpanel in an attached garage

Load current: 100 A · Circuit voltage: 240 V · One-way distance: 40 ft · Wire type: THHN/THWN wires in conduit (75 °C)

Wire size
3 AWG copper
Current the wire must carry
100.0 A
Rated for
100 A
Voltage drop
0.82%
Longest run within 3%
147 ft

A detached workshop across the yard

Load current: 100 A · Circuit voltage: 240 V · One-way distance: 150 ft · Conductor: Aluminum

Wire size
1/0 AWG aluminum
Current the wire must carry
100.0 A
Rated for
120 A
Voltage drop
2.51%
Longest run within 3%
179 ft

A basement subpanel for a finished room

Load current: 100 A · Circuit voltage: 240 V · One-way distance: 25 ft · Conductor: Aluminum

Wire size
1 AWG aluminum
Current the wire must carry
100.0 A
Rated for
100 A
Voltage drop
0.53%
Longest run within 3%
142 ft

Feeder size for a 100 amp subpanel by one-way distance

One-way distanceCopper, THHN/THWN wires in conduit (75 °C)Aluminum
25 ft3 AWG1 AWG
50 ft3 AWG1 AWG
100 ft3 AWG1 AWG
150 ft2 AWG1/0 AWG
200 ft1 AWG2/0 AWG

Each cell: the smallest conductor rated for a hundred amps in the higher temperature column that keeps the drop within the branch-circuit limit.

Why a subpanel feeder is bigger than a service

The code lets the service conductors of a single-family house carry only 83 percent of their rating, because a whole home never draws its full service at once. A subpanel feeds part of the house or another building, so it gets no such allowance and is sized from the regular ampacity table: 3 AWG copper carries 100 amps and 1 AWG aluminum 100 amps. Compare the 100 amp service page, where the same rating takes smaller wire.

Why NM-B cable does not appear here

NM-B cable is rated from the lowest temperature column, where copper does not reach one hundred amps in the sizes this cable is made in. A 100 amp feeder is therefore run as single conductors in conduit, as SER cable inside the house, or as aluminum cable rated for burial to a detached building. Each needs two hots, a neutral and a ground, with the neutral and ground bars kept apart in the subpanel.

Distance and a detached building

A feeder is usually held to about 2 percent of drop, tighter than a branch circuit. Over a long trench that pushes the size up a step or two, and the table shows where. A detached building also needs its own grounding electrode and a disconnect. The breaker in the main panel stays at 100 amps when you upsize the wire.

Common questions

What size wire for a 100 amp subpanel?

3 AWG copper or 1 AWG aluminum, rated 100 amps and 100 amps in the higher temperature column, on a short run. A long run may need the next size up.

Can I use 4 AWG copper for a 100 amp subpanel?

No. 4 AWG copper is rated 85 amps. It appears for a 100 amp house service only because the service is sized for 83 percent of its rating, and a subpanel is not.

What size aluminum wire for a 100 amp subpanel 150 feet away?

Over that distance voltage drop usually sets the size rather than the current: enter it above to see the answer, typically one or two sizes larger than the short-run 1 AWG.

Does a 100 amp subpanel need 4 wires?

Yes: two hots, a neutral and an equipment ground. The neutral bar in the subpanel must not be bonded to the ground bar.