FigureYard
Electrical, Heating & Insulation

Wire Size for a 100 Amp Service

The service conductors for a 100 amp single-family house can be 4 AWG copper or 2 AWG aluminum. The code allows them to carry 83 percent of the service rating, because a home never draws its whole service at once, so they are a size smaller than a feeder of the same rating. That allowance covers only the conductors that carry the entire load of one dwelling.

Reviewed by FigureYard editorial teamUpdated October 13, 20267 sources

Your measurements

Remembered on this device
A
V
Conductor
More options
%
Wire size
4 AWGcopper
  • Current the service wire must carry: 83.0 A
  • Rated for: 85 A
  • Voltage drop: 1.03%
  • Longest run within 3%: 117 ft
Each copper size for this circuit
SizeRatedDropFits
10 AWG30 A4.13%Too small for the current
8 AWG50 A2.59%Too small for the current
6 AWG65 A1.64%Too small for the current
4 AWG85 A1.03%Yes
3 AWG100 A0.82%Yes
2 AWG115 A0.65%Yes

4 AWG copper service conductor (83% of the rating, 75 °C column) is the smallest size here; the service rating sets it. A service that feeds a whole single-family house may be sized for 83% of its rating (NEC 310.12); a feeder to a subpanel or a detached building is not, so choose a circuit or a subpanel for that. This uses the base table: hot attics, more than three current-carrying wires together, and the terminals on your breaker and devices can call for a larger size. Have an electrician or your inspector confirm the circuit.

The calculator is set to a whole-house service at 100 amps and 240 volts. Enter the distance from the meter to the panel and choose the metal to see the size, and whether a long run calls for more.

How to use this calculator

  1. Leave the rating at 100 amps, the main breaker of the house.
  2. Choose copper or aluminum. Most new services use aluminum SE or USE cable.
  3. Enter the one-way distance from the meter or the service disconnect to the main panel.
  4. For a subpanel or a detached building, switch to a circuit or a subpanel: the service allowance does not apply there.

Worked examples

A meter on the outside wall, panel just inside

The wire feeds: A whole house (service) · Load current: 100 A · Circuit voltage: 240 V · One-way distance: 15 ft · Conductor: Aluminum

Wire size
2 AWG aluminum
Current the service wire must carry
83.0 A
Rated for
90 A
Voltage drop
0.40%
Longest run within 3%
113 ft

A meter on a pole at the edge of the lot

The wire feeds: A whole house (service) · Load current: 100 A · Circuit voltage: 240 V · One-way distance: 140 ft · Conductor: Aluminum

Wire size
1 AWG aluminum
Current the service wire must carry
83.0 A
Rated for
100 A
Voltage drop
2.95%
Longest run within 3%
142 ft

A copper service in an older house

The wire feeds: A whole house (service) · Load current: 100 A · Circuit voltage: 240 V · One-way distance: 30 ft

Wire size
4 AWG copper
Current the service wire must carry
83.0 A
Rated for
85 A
Voltage drop
0.77%
Longest run within 3%
117 ft

Service conductor size for a 100 amp dwelling by distance

One-way distanceCopperAluminum
25 ft4 AWG2 AWG
50 ft4 AWG2 AWG
100 ft4 AWG2 AWG
150 ft2 AWG1/0 AWG
200 ft1 AWG2/0 AWG

Each cell: the smallest conductor under the dwelling service rule that also keeps the drop at full rated current within the branch-circuit limit.

The dwelling service rule

NEC Table 310.12 lists the service sizes for one-family homes, and the rule behind it is simple: the conductors must carry 83 percent of the rating. For a service of 100 amps the table gives 4 AWG copper, rated 85 amps, or 2 AWG aluminum, rated 90 amps. It applies to the service entrance conductors and to the main feeder that carries the whole house's load, single-phase, without heat or bundling corrections.

When the allowance does not apply

A feeder to a subpanel, a detached garage or one wing of the house is sized from the regular ampacity table at the full rating: see the 100 amp subpanel page, where the answer is 3 AWG copper or 1 AWG aluminum. A duplex served by one set of conductors, a three-phase service and a hot attic run all fall outside the rule too.

Upgrading from a 100 amp service

Many older homes have exactly this service. A heat pump, a car charger or an electric range can push the load past it, and the usual step up is a 200 amp service with new service conductors, meter base and panel, arranged with the utility. A load calculation by an electrician tells you whether the upgrade is needed; the amps calculator helps total up the big appliances first.

Common questions

What size wire for a 100 amp service?

4 AWG copper or 2 AWG aluminum for the service of a single-family house, under NEC Table 310.12, which sizes the conductors for 83 percent of the rating.

Is 2 AWG aluminum good for 100 amp service?

Yes, for a whole-house service: it is rated 90 amps, above the share of the rating the dwelling rule asks for. For a 100 amp subpanel it is too small; that needs 1 AWG aluminum.

Can I use 4 AWG copper for 100 amps?

For the service of a single-family house, yes. For any other 100 amp feeder, no: 4 AWG copper is rated 85 amps and the feeder must carry the full hundred.

Does the distance to the meter change the size?

On a long run, yes. With a meter on a pole far from the house, voltage drop can call for a larger size; enter the distance above to check.